Feature
- S7-200 CPU models CPU 221, CPU 222, CPU 224, CPU 224XP, and CPU 226 to include: New CPU hardware support (option to turn off run mode edit to get more program memory, CPU 224XP supports onboard analog I/O and two communication ports. CPU 226 includes additional input filters and pulse catch)
- New memory cartridge support: S7-200 Explorer browser utility, memory cartridge transfers, compares, and programming selections
- STEP 7--Micro/WIN, version 4.0, a 32-bit programming software package for the S7-200 to include:
New and improved tools that support the latest CPU enhancements: PID Auto-Tuning Control Panel, PLCs built-in Position Control Wizard, Data Log Wizard, and Recipe Wizard
New diagnostic tool: configuring diagnostic LED
New instructions: Daylight Savings time (READ_RTCX and SET_RTCX), Interval Timers (BITIM, CITIM), Clear Interrupt Event (CLR_EVNT), and Diagnostic LED (DIAG_LED)
POU and library enhancements: new string constants, added indirect addressing support
on more memory types, improved support of the USS library read and write parametization for Siemens master drives
Improved Data Block: Data Block Pages, Data Block auto-increment
Improved usability of STEP 7--Micro/WIN
Specifications
Power supply |
20,4~28,8V DC; 85~264V AC (47~63Hz) |
Number of I/O points |
6 DI/4 DO; 8 DI/6 DO; 14 DI/10 DO; 14 DI/10 DO/ 2 AI/1 AO; 24 DI/16 DO |
Digital inputs/outputs/max. number of channels with expansion modules |
48/46/94; 114/110/224; 114/110/224; 128/128/256 |
Analog inputs/outputs/max. number of channels with expansion modules |
16/8/16; 32/28/44; 2 AI/1 AO integrated 32/28/44; 32/28/44 |
Program memory |
4; 8/12; 12/16; 16/24 KByte |
Data memory |
2; 8; 10 KByte |
Programming software |
STEP 7-Micro/WIN supports all standards such as STL, CSF or LAD |
Communication port |
RS 485 interface supporting the following operating modes: PPI master or slave/MPI, slave/Freeport (freely configurable ASCII protocol), Modbus Master/Slave |
Class of protected |
IP 20 |
Ordering information
Connections