Type |
Voltage and phase protection relays |
Protection function |
Overvoltage, Undervoltage, Phase-failure, Phase sequence (Phase reversed), Phase unbalance (Asymmetry), PTC temperature |
Display type |
LED indicator |
Number of phase |
3-phase |
Rated supply voltage |
380VAC |
Operating frequency |
50Hz |
Rated input voltage |
380...415VAC |
Undervoltage setting (% Rated input voltage) |
70...95% |
Overvoltage setting (% Rated input voltage) |
105...130% |
Asymmetry setting (% Rated input voltage) |
5...15% |
Operating time of overvoltage/undervoltage |
0.1...10s |
Operating time of phase sequence |
1s max. |
Operating time of asymmetry |
0.1...10s |
Reset method |
Automatic |
Rated contact capacity (resistive load) |
0.75A at 240VAC, 0.47A at 415VAC |
Case material |
Plastic |
Connections type |
Screw terminals |
Mounting type |
DIN rail mounting |
Operating ambience |
Standard |
Overall width |
35.8mm |
Overall height |
66.2mm |
Overall depth |
91mm |
Representative standard |
EN, IEC |
Standard accessories |
Updating |
Separately accessories |
DIN tracks: PFP-100N, DIN tracks: PFP-50N, DIN-rail: HYBT-01, DIN-rail: PFP-100N, DIN-rail: TC 5x35x1000-Aluminium, DIN-rail: TC 5x35x1000-Steel, Stopper: BIZ-07, Stopper: BNL6, End plate: PFP-M |