Type |
Voltage and phase protection relays |
Protection function |
Undervoltage, Overvoltage, Phase unbalance (Asymmetry), Phase sequence (Phase reversed), Phase loss |
Display type |
LED indicator |
Number of phase |
3-phase |
Rated supply voltage |
200VAC, 220VAC, 230VAC, 240VAC, 380VAC, 400VAC, 415VAC, 480VAC |
Operating frequency |
50Hz, 60Hz |
Rated input voltage |
200VAC, 220VAC, 230VAC, 240VAC, 380VAC, 400VAC, 415VAC, 480VAC |
Undervoltage setting (% Rated input voltage) |
102...130% |
Overvoltage setting (% Rated input voltage) |
102…130% |
Asymmetry setting (% Rated input voltage) |
105…122% |
Operating time of overvoltage/undervoltage |
0.1...30s |
Operating time of phase sequence |
0.1s |
Operating time of phase loss |
0.1s |
Operating time of asymmetry |
0.1...30s |
Reset method |
Automatic |
Output configuration |
SPDT |
Rated contact capacity (resistive load) |
5A at 250VAC, 5A at 30VDC |
Case material |
Plastic |
Connections type |
Screw terminals |
Mounting type |
DIN rail mounting |
Operating ambience |
Standard |
Ambient temperature |
-20...60°C |
Ambient humidity |
25...85% |
Approx. weight |
65g |
Overall width |
17.5mm |
Overall height |
80mm |
Overall depth |
74mm |
Degree of protection |
IP20 |
Representative standard |
UL, CCC, CSA, CE, KC |