Features
- Yaskawa Inverter GA700 has the most advanced drive technology.
- Powerful Starting Torque without Encoder
- Torque Control without Encoder
- EZ Open Loop Vector Control Tuning-less even for Synchronous Motors!
- High-speed Operation
- Built-in Power Supply for the Sensor, Braking Transistor, DC Reactor, EMC Filter (C2, C3),
- Peripheral Parts Reduction
- Condition Confirmation of Malfunction Without The Main Circuit Power Supply
- Support Tool “DriveWizard”*
- Smartphone Application “DriveWizard Mobile
- Certified Standards: CE, UL, cUL, KC, RCM, NK, GL
- Inverter GA700, Energy Saving, Environmental Features, Safety.
Specifications
Application of Inverter Yaskawa GA700 |
ND: Fans, Pumps, HVAC |
Power supply |
3P, 200 to 240Vac, 380 to 480Vac (− 15% to +10%) 50/60 Hz (± 5%) |
Rated capacity |
0.4-90 kW (200 V), 0.4-315 kW (400 V) |
Rated current |
4.8-360 A (200V), 2.5-675 A (400V) |
Output frequency range |
0-590 Hz |
Starting Torque |
150 %/3 Hz (V/f Control and Closed Loop V/f Control) |
Overload current rating |
ND Rating: 110 % of rated output current for 60 s, HD Rating: 150 % of rated output current for 60 s (Derating may be required for applications that start and stop frequently) |
Control Method |
V/f Control, V/f Control with PG, Open Loop Vector Control, Closed Loop Vector Control, Open Loop Vector |
Braking unit |
All models up to 75 kW are equipped with a brak -ing transistor for even more powerful braking op -tions by just adding a braking resistor. |
Input |
Multi-Function Digital Input, Main Frequency Reference Input, Safety Input |
Ouput |
Multi-Function Photocoupler Output, Fault Relay Output, Multi-Function Digital Output, Monitor Output, , Safety Monitor Output |
Protection Function |
Motor Protection, Momentary Overcurrent Protection, Overload Protection, Overvoltage Protection, Undervoltage Protection, Momentary Power Loss Ride -Thru, Heatsink Overheat Protection, Braking Resistance Overheat Protection, Stall Prevention, Ground Fault Protection: Protection by electronic circuit |
Main Control Functions |
Torque Control, Droop Control, Speed/Torque Control switch, Feed Forward Control, Zero Servo Control, Momen-tary Power Loss Ride -Thru, Speed Search, Overtorque detection, torque limit, 17 Step Speed (max.), accel/decel time switch, S-curve accel/decel, 3-wire sequence, Auto-Tuning (rotational, stationary), Online Tuning, Dwell, cool-ing fan on/off switch, slip compensation, torque compensation, Frequency Jump, Upper/lower limits for frequency reference, DC Injection Braking at start and stop, Overexcitation Deceleration, High Slip Braking, PID control (with Sleep function), Energy Saving Control, MEMOBUS comm. (RS-485 /422 , max. 115 .2 kbps), Fault Restart, Appli-cation Presets, DriveWorksEZ (customized functions), Removable Terminal Block with Parameter Backup... |
Communication |
RS485 (MEMOBUS/Modbus at 115 .2 kbps) standard on all models. |
Peripheral Devices and Options |
LCD Operator, AC Reactor, DC Reactor, Braking Unit, Braking Resistor, noise filter... |
Degree of protection |
Open-chassis type IP20 |