Type |
Earth leakage circuit breaker (ELCB) |
Number of poles |
2P |
Frame size |
100AF |
Rated current (In) |
40A |
Line voltage |
AC |
Rated operational voltage (Ue) |
220VAC, 460VAC |
Rated frequency |
50Hz, 60Hz |
Rated residual current |
100/300/500/1000mA |
Automatic tripping device |
Thermal-magnetic |
Breaking capacity |
50kA |
Service breaking capacity - Ics (% Icu) |
100% |
Protection delay time |
0.1/0.4/1/2s |
Protection function |
Ground fault , Overcurrent, Short-circuit |
On/Off control type |
Handle toggle |
Mounting method |
Surface mounting |
Connection type |
Screw terminals, Rear connection |
Approx. net weight |
800g |
Overall width |
75mm |
Overall height |
130mm |
Overall depth |
68mm |
Representative standard |
IEC |
Separately accessories |
Auxiliary/Alarm (AXT):AXT 10GM R1 |
Shunt trip (Sold separately) |
SHT 10GM DC24V, SHT 10GM DC100-120V, SHT 10GM DC48V, SHT 10GM DC60V, SHT 10GM DC125V, SHT 10GM AC200-250V, SHT 10GM AC380-480V |
Under voltage trip (Sold separately) |
UVT 10GM DC24V, UVT 10GM DC48V, UVT 10GM AC200-230V, UVT 10GM AC380-415V, UVT 10GM AC440-480V |
Auxiliary switch (Sold separately) |
AUX 10GM C1, AUX 10GM C2 |
Alarm switch (Sold separately) |
ALT 10GM L1, ALT 10GM R1 |
Mechanical interlock (Sold separately) |
MIF 10GM 2 |
Rotary handle (Sold separately) |
TFG 10GM L, TFG 10GM R, TFG 10GM U, TFH 10GM |
Other option (Sold separately) |
TDA 10GM D2, CBM 10GM 2P UNIT, RCT 05GM F2, RCT 10GM F2, CTB 10GM 2S50, CTB 10GM 2S100, CTB 10GM 2S50 - MM, CTB 10GM 2S100 - MM, DRA 10GM, TCF 10GM S2, TCF 10GM L2, PLD 10GM, MIF 10GM 2, TQQ 10GM 2 |