Earth leakage circuit breakers HYUNDAI
3P; 160A; 100/300/500/1000mA; 26kA
Manufacturer: HYUNDAI
Item Status: Contact us
 Customer support hotline for products:
Northern Region, North Central Region:
Southern Region, South Central Region:
 5

Series: Earth leakage circuit breakers HYUNDAI HGE series

Model: HGE250S 3P 160A

Features of Earth leakage circuit breakers HYUNDAI HGE series (contains model HGE250S 3P 160A)

Specifications of Earth leakage circuit breakers HYUNDAI HGE250S 3P 160A

Type

Earth leakage circuit breaker (ELCB)

Number of poles

3P

Frame size

250AF

Rated current (In)

160A

Line voltage

AC

Rated operational voltage (Ue)

220VAC, 460VAC

Rated frequency

50Hz, 60Hz

Rated residual current

100/300/500/1000mA

Automatic tripping device

Thermal-magnetic

Breaking capacity

26kA

Service breaking capacity - Ics (% Icu)

100%

Protection delay time

0.1/0.4/1/2s

Protection function

Ground fault , Overcurrent, Short-circuit

On/Off control type

Handle toggle

Mounting method

Surface mounting

Connection type

Screw terminals, Rear connection

Approx. net weight

1.5kg

Overall width

105mm

Overall height

165mm

Overall depth

68mm

Representative standard

IEC

Separately accessories

Auxiliary/Alarm (AXT):AXT 10GM R1

Shunt trip (Sold separately)

SHT 10GM DC24V, SHT 10GM DC100-120V, SHT 10GM DC48V, SHT 10GM DC60V, SHT 10GM DC125V, SHT 10GM AC200-250V, SHT 10GM AC380-480V

Under voltage trip (Sold separately)

UVT 10GM DC24V, UVT 10GM DC48V, UVT 10GM AC200-230V, UVT 10GM AC380-415V, UVT 10GM AC440-480V

Auxiliary switch (Sold separately)

AUX 10GM C1, AUX 10GM C2

Alarm switch (Sold separately)

ALT 10GM L1, ALT 10GM R1

Mechanical interlock (Sold separately)

MIF 25GM 3

Rotary handle (Sold separately)

TFH 25GM, TFG 25GM L, TFG 25GM R, TFG 25GM U

Other option (Sold separately)

TDM 25GM P3, TDM 25GM F3, CBM 10GM UNIT, TBB 25GP 3S, TBB 25GP 3E45, RCT 25GM F3 LINE, RCT 25GM F3 LOAD, CTB 25GM 3S, CTB 25GM 3S - MM, TCF 25GM S3, TCF 25GM L3, PLD 10GM, TQQ 25GM 3, MOT 25GM DC24 V, MOT 25GM AC/DC110 V, MOT 25GM AC/DC240 V

Document of Earth leakage circuit breakers HYUNDAI

Comment about product
Loading  Processing, please wait ...
Contact us now

 Bao An Automation

Bao An Technique Service Joint Stock Company
Address: 3A Ly Tu Trong, Minh Khai, Hong Bang, Hai Phong, Viet Nam
Haiphong Office and Warehouse: Van Tra B project area, An Dong, An Duong Dist., Haiphong City, Vietnam
Hanoi Office and Warehouse: No. 3/38, Chu Huy Man Str., Phuc Dong Ward, Long Bien Dist., Hanoi City, Vietnam
Ho Chi Minh Office and Warehouse: No. 204, No Trang Long Str., Ward 12, Binh Thanh Dist., Ho Chi Minh City, Vietnam
Factory: Van Tra B project area, An Dong, An Duong, Hai Phong, Viet Nam
Hotline: (+84) 989 465 256 (South) / (+84) 936 862 799 (North)
Tax code: 0200682529 - Date: 31/07/2006
 Designed by Bao An Technique Service Joint Stock Company
 Email: baoan@baoanjsc.com.vn -  Curent online: 34 -  Total visited: 120.077.082
Chat hỗ trợ