Type |
Earth leakage circuit breaker (ELCB) |
|
Number of poles |
4P |
|
Frame size |
100AF |
|
Rated current (In) |
30A |
|
Line voltage |
AC |
|
Rated operational voltage (Ue) |
220VAC, 460VAC |
|
Rated frequency |
50Hz, 60Hz |
|
Rated residual current |
100/200/500mA |
|
Tripping characteristics (Curve) |
c |
|
Breaking capacity |
18kA |
|
Ultimate breaking capacity (Icu) |
18kA at 460VAC |
|
Service breaking capacity - Ics (% Icu) |
100% |
|
Protection delay time |
0.1s |
|
Protection function |
Ground fault , Overcurrent, Short-circuit |
|
On/Off control type |
Handle toggle |
|
Mounting method |
Surface mounting |
|
Connection type |
Screw terminals |
|
Approx. net weight |
900g |
|
Overall width |
100mm |
|
Overall height |
130mm |
|
Overall depth |
82mm |
|
Representative standard |
CE |
|
Standard accessories |
Bolts/Screws |
|
Separately accessories |
Alarm switch: AL, Auxiliary switch: AX, Combination switch: AX+AL, Handle lock, Insulation barrier: IB13, Rear terminal (Bar): RTB1, Rear terminal (Round): RTR1, Rotary handle (Driect): DH100, Rotary handle (Extended): EH100, Rotary handle: N-30c, Terminal cover (Long): TCL13, Terminal cover (Short): TCS13, Rotary handle (Direct, key lock): DHK100 |